Testing of power transformers makes a couple of different measurements necessary, which are described in the international IEC 60076 standard.
Scope and Vector Scope offer the capability to analyze the voltage ratio and phase displacement of different primary and secondary configurations (star, delta, interconnected star).
Transient recording functionality allows storing all signals at the full sampling rate for detailed analysis. In combination with the trigger functionality failures and transient events (also during long-term measurements of the transformer) can easily be detected.
The Power quality module allows measuring harmonics of the voltage and the current up to some hundred kHz. The data can be represented in percentage of the fundamental frequency as required for the no-load current according to IEC 60076 standard.
The power quality module also automatically calculates the zero-sequence impedance which is required in the power transformer testing.
The math library allows to automatically calculate parameters like the magnetizing current, the iron losses, the main inductance for example out of the no-load test or the stray inductances out of the short-circuit tests.
For more information check the power quality application page.
Power and efficiency analysis of the transformers require the highest accuracy of the power calculation for all phase angles. Especially analysis at lower power factors is very difficult with conventional measurement equipment.
The additional sensor calibration functionality allows correcting the behavior of voltage and current transducers for amplitude and phase over the whole frequency range.
Furthermore, IEC 60076-1 standard requires the correction of measured power losses depending on the temperature. Dewesoft power analyzer makes it easy to measure all the required temperatures (winding, oil, ambient, etc.) perfectly synchronized to voltage, current and other measured parameters.
In addition, it’s possible to automatically calculate the corrected power losses. You can also measure the power of oil pumps and fan motors, and even the sound level of the transformer according to IEC 60551 standard.
This covers all the possible tests that you can experience with power transformers, and Dewesoft can cover them all with one single device.
Analysis according to IEC 60076 standard
Correction of power losses depending on temperature
Additional software sensor calibration
Measure harmonics and symmetrical components
For the most typical configuration, we suggest R2DB DAQ system with optional additional KRYPTON DAQ for temperature inputs:
Système d'acquisition de données ultra compact et mobile avec enregistreur intégré, PC industriel de traitement des données, écran tactile et batteries internes pour une portabilité maximale.
Capteurs haute précision pour la mesure du courant AC / DC et l'analyse de la puissance. Des pinces de courant, aux transducteurs de courant Zéro Flux haute précision et aux bobines de Rogowski.
Dewesoft X est le meilleur logiciel d’acquisition, d’enregistrement et d’analyse de données au monde. Le logiciel a reçu de nombreux prix internationaux, il est innovant, convivial, intuitif et riche en fonctionnalités
La solution Dewesoft peut mesurer tous les paramètres de qualité d’alimentation conformément à la norme IEC 61000-4-30 Classe A. Par rapport à d’autres analyseurs de qualité d’énergie, il est possible de réaliser une analyse plus détaillée (par exemple, stockage de données brutes, comportement en cas de défaillance, calcul de paramètres supplémentaires, etc.).